    Voltage Drop Calculator

    Check whether your wire is big enough. Pick an AWG size (14–4), enter one-way run length, current and system voltage, and get voltage drop in volts and percent, the delivered voltage at the load, power lost in the cable, and a good/borderline/excessive verdict with a full AWG comparison table.

    #voltage drop calculator#wire size#awg#cable loss#nec voltage drop

    TheCalculators — Voltage Drop Calculator

    Printed thecalculators.com

    Presets
    ft
    10500
    A
    1100
    V
    11,000

    Live mode: results update as you type.

    Voltage Drop

    4.76 V

    3.97% of 120 V · ≈ 115.24 V at the load

    Wire
    12 AWG copper
    Resistance
    1.588 Ω per 1000 ft
    One-Way Length
    100 ft
    Phase Factor
    2 (single phase, out & back)
    Load Current
    15 A
    Drop (V)
    4.76
    Drop (%)
    3.97%
    Delivered Voltage
    115.24 V
    Power Lost in Cable
    71.5 W
    Verdict
    Borderline

    Voltage drop verdict

    4.0%

    Borderline (3–5%)

    Good (< 3% NEC target)< 3Borderline (3–5%)3–5Excessive (≥ 5%)5–10

    How the drop is computed

    1. 1FormulaVD = 2 × I × L × R ÷ 1000 (single phase: out and back)
    2. 2Substitute2 × 15 A × 100 ft × 1.588 ÷ 1000 = 4.764 V
    3. 3Percent of source4.764 ÷ 120 × 100 = 3.97%
    4. 4Cable heating lossVD × I = 4.764 × 15 = 71.5 W wasted as heat

    Every gauge at this run length & current

    AWGΩ per 1000 ftDrop (V)Drop (%)Verdict
    142.5257.586.31%Excessive
    121.5884.763.97%Borderline
    100.99932.50%Good
    80.6281.881.57%Good
    60.3951.190.99%Good
    40.2490.750.62%Good

    Same length, current and phase — only the conductor size changes.

    Uses uncoated copper resistance at 75 °C per NEC Chapter 9 Table 8. The NEC recommends ≤ 3% for a branch circuit and ≤ 5% combined feeder + branch. Aluminum conductors need larger sizes.

    Most useful next

    Voltage Drop

    4.76 V

    Formula

    VD = k × I × L × R ÷ 1000 · k = 2 (1φ) or √3 (3φ) · R = Ω per 1000 ft · % = VD ÷ source V × 100

    Pro tips

    • • Long runs are the silent killer: doubling length doubles drop — check before adding a shed or EV charger circuit.
    • • If you are above 3%, jump two wire sizes rather than one; resistance falls roughly 40% per size step.

    FAQ

    Related Calculators

    More Everyday tools you might need.

    Ohms Law Calculator

    Enter any two of voltage, current and resistance to solve the third — plus power in watts.

    Calculate

    Electricity Calculator

    Estimate appliance electricity usage and cost per day, month and year from watts and hours.

    Calculate

    Resistor Calculator

    Decode a 4-band resistor color code into resistance, tolerance and min/max range.

    Calculate

    Btu Calculator

    Estimate the air-conditioner BTU/h you need for any room based on size, sun and insulation.

    Calculate
    TheCalculatorsCalculate Anything. Anytime.

    Your all-in-one destination for free online calculators. Simple. Fast. Accurate. Always here for you.

    Quick Links

    • Home
    • All Calculators
    • Categories
    • Blog
    • About Us
    • Contact

    Popular Categories

    • Health Calculators31
    • Finance Calculators62
    • Education Calculators9
    • Travel Calculators8
    • Everyday Calculators65
    • Developer Calculators7

    Resources

    • Calculator Guide
    • Tips & Tutorials
    • Calc of the Day
    • FAQs
    • Privacy Policy
    • Terms of Service
    • Sitemap

    © 2026 TheCalculators. All rights reserved. · 204 free tools and counting.

    Calculate Anything, Anytime.Made for a Smarter World

    /orCtrl Kto searchEscto close dialogsEnterto calculate